TC-CG

TC-CG is a CASMO thermocouple wire for Thermocouple Wire. Fiberglass insulated, 0°C to +480°C. Compact 2-core parallel flat thermocouple wire with thin-wall wrapped fiberglass core insulation and silicone-resin-finished fiberglass overall braid (0°C to +480°C).

Compact 2-core parallel flat thermocouple wire with thin-wall wrapped fiberglass core insulation and silicone-resin-finished fiberglass overall braid (0°C to +480°C).

Key Ratings

  • TC-CG: · Temperature 0°C to +480°C

Construction

Conductor
Thermocouple Alloy (Type K / N / E / J) · Stranded
Core Insulation
Wrapped · Fiberglass
Cabling
Parallel · Duplex parallel flat core pair
Core Identification
Color-coded fiberglass tracer per IEC 60584-3 (Type K: +White w/ Green tracer / -White) or ASTM E230 on request
Jacket
Braided · Fiberglass

Characteristics

  • Short-Term Peak Temperature: +540°C (single-exposure E-glass limit)
  • Saturant & Tracer Volatilization: Silicone resin saturant and organic dye tracers volatilize or fade above +204°C while braided fiberglass maintains continuous electrical separation up to +480°C; retain polarity tags at cold terminations.
  • Signal Circuit Duty: Dry-location low-voltage thermoelectric millivolt EMF measurement circuits only; porous fiberglass insulation is not voltage-rated for mains power circuits.
  • Calibrated EMF Accuracy: Matched thermoelectric conductor pairs maintain stable electromotive force characteristics across the rated temperature span.
  • Ultra-Thin Compact Profile: Compact parallel duplex geometry reduces bundle cross-section for tight sensor feedthroughs, vacuum chambers and test fixtures.
  • High-Temperature Thermal Stability: Heat-resistant insulation and jacketing resist thermal aging, embrittlement and cut-through in elevated-temperature zones.
  • Flexibility: Flexible construction facilitates routing, bending and installation where space is limited.

Applications

  • Industrial Furnaces, Kilns and Heat Treatment: For temperature measurement and extension wiring on heat-treating furnaces, ceramic kilns, ovens and thermal processing lines.
  • Autoclaves, Cryogenic Chambers and Test Rigs: For precision thermal profiling in aerospace autoclaves, environmental test chambers, semiconductor tools and laboratory instrumentation.
  • Sensors and Instrumentation: For connections between sensors, measuring instruments and associated control equipment.

Standards & Compliance

  • Standard: IEC 60584-1 / ASTM E230
  • RoHS: Compliant
  • REACH: Compliant

TC-CG — Thin-Wall Wrapped + Braided Fiberglass 480°C Wire

CASMO Part No.Total CoresConductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Conductor Dia. (mm)Nom. Ins. Thickness (mm)Nom. Core O.D. (mm)Nom. Jkt. Thickness (mm)Nom. Overall Width (mm)Overall Width Tolerance ± (mm)Nom. Overall Thickness (mm)Overall Thickness Tolerance ± (mm)
710232C26-K-XX22670.160.480.130.740.21.90.21.10.2
710232C24-K-XX22470.20.60.130.860.22.10.21.30.2
710232C22-K-XX22270.2540.760.131.020.22.40.21.40.2
710232C20-K-XX22070.320.960.131.220.22.80.21.60.2
710232C18-K-XX21870.391.170.131.430.23.30.21.80.2
710232C16-K-XX216190.31.50.131.760.23.90.22.20.2
710232C14-K-XX214190.371.850.132.110.24.60.22.50.2

* "-K-" = Type K thermocouple-grade alloy pair (NiCr / NiAl, standard). Substitute "-N-" (Type N), "-E-" (Type E), or "-J-" (Type J; note wire-gauge oxidation limit: 26–24 AWG ≤ +370°C, 22–20 AWG ≤ +480°C). Extension-grade alloys and Type T are not supplied for +480°C fiberglass service. † "-XX" = color-code suffix: IEC 60584-3 fiberglass tracer code supplied as standard (e.g., GN for Type K); ASTM E230 tracer code available upon request (see Color Code Chart below). Organic dye tracers and silicone saturant volatilize/fade above +204°C; retain polarity tags at cold terminations.

  • "-K-" = Type K thermocouple-grade alloy pair (NiCr / NiAl, standard). Substitute "-N-" (Type N), "-E-" (Type E), or "-J-" (Type J; note wire-gauge oxidation limit: 26–24 AWG ≤ +370°C, 22–20 AWG ≤ +480°C). Extension-grade alloys and Type T are not supplied for +480°C fiberglass service.
  • "-XX" = color-code suffix: IEC 60584-3 fiberglass tracer code supplied as standard (e.g., GN for Type K); ASTM E230 tracer code available upon request (see Color Code Chart below). Organic dye tracers and silicone saturant volatilize/fade above +204°C; retain polarity tags at cold terminations.

Color Code Chart

  • +White w/ Green tracer / -White (Jkt: White w/ Green tracer)
  • +White w/ Black tracer / -White (Jkt: White w/ Black tracer)
  • +White w/ Violet tracer / -White (Jkt: White w/ Violet tracer)
  • +White w/ Pink tracer / -White (Jkt: White w/ Pink tracer)
  • +Yellow tracer / -Red tracer (Jkt: Brown or Yellow tracer)
  • +White / -Red tracer (Jkt: Brown or Black tracer)
  • +Purple tracer / -Red tracer (Jkt: Brown or Purple tracer)
  • +Orange tracer / -Red tracer (Jkt: Brown or Orange tracer)

Related Categories