IEC 60584 — International Thermocouple & Extension Cables

Global standard governing thermocouple EMF reference tables (Part 1), Class 1 / Class 2 accuracy tolerances and polarity colour identification (Part 3 — negative conductor always White).

Standard · International Electrotechnical Commission (IEC)

What is IEC 60584?

IEC 60584 is the global benchmark for thermocouple temperature measurement, harmonised across Europe as EN 60584 / DIN EN 60584 / BS EN 60584 (superseding DIN 43710, BS 4937 and NF C 42-324). Part 1 defines reference EMF voltage tables for letter-designated calibrations (Types K, J, T, E, N, R, S and B), while Part 3 governs extension (X) and compensating (C) cables linking sensors to control instrumentation.

Under IEC 60584-3, cable accuracy divides into Class 1 (tighter tolerance, e.g., ±1.5°C for KX/JX/EX from −25°C to +200°C) and Class 2 (±2.5°C). For unambiguous field wiring, IEC 60584-3 mandates that the negative leg is ALWAYS White while the positive leg and outer jacket carry the calibration colour (Green for K, Black for J, Brown for T, Violet for E, Pink for N, Orange for R/S; light blue sheath for Ex i intrinsically safe loops).

Key Technical Requirements

ParameterRequirementNotes
Tolerance classesClass 1 (±1.5°C KX/JX) · Class 2 (±2.5°C)Defined over −25°C to +200°C for extension cables
Polarity codingNegative ALWAYS WhitePositive & jacket: K=Green, J=Black, T=Brown, E=Violet, N=Pink, R/S=Orange
DesignationsThermocouple · Extension (X) · Comp. (C)Extension matches alloy; compensating substitutes for noble metals
Intrinsically safeLight blue outer sheathMandated under IEC 60584-3 for Ex i loops

Frequently Asked Questions

What is the difference between extension (-X) and compensating (-C) cables under IEC 60584-3?
Extension cables (KX, JX, TX, EX, NX) use conductors of the same nominal alloy composition as the thermocouple, whereas compensating cables (RCA/RCB, SCA/SCB, KCA/KCB) use cost-effective alternative copper/nickel alloys calibrated to replicate the sensor's EMF curve over ambient routing.
How can I tell an IEC 60584-3 cable from an ANSI/ASTM cable immediately?
Check the negative conductor colour: IEC 60584-3 negative legs are ALWAYS White (Type K = Green + / White −), whereas ASTM/ANSI negative legs are ALWAYS Red (Type K = Yellow + / Red −).