Thermocouple & RTD Cables
Calibration-matched thermocouple, extension and compensating cables alongside 3- and 4-wire PT100 RTD sensor cables — built to IEC 60584, ASTM E230 / ANSI MC96.1 and IEC 60751 from −190°C to +1200°C.
Thermoelectric calibration, polarity standards & thermal tiers
Temperature-sensing loops cannot substitute ordinary copper hook-up wire for thermocouple conductors. Because a thermocouple measures microvolt Seebeck potentials across dissimilar metal alloys, the cable linking the sensor head to transmitters, PLCs or PID controllers must match the circuit's thermoelectric EMF curve without introducing parasitic junctions. International procurement is governed primarily by IEC 60584 (Parts 1 and 3, harmonised as EN 60584) and North American ASTM E230 / E230M (incorporating ANSI/ISA MC96.1), while industrial platinum resistance thermometers (PT100 / PT1000 RTDs) follow IEC 60751 using matched copper or nickel-plated copper leads in 3-wire (2 Red + 1 White) and 4-wire (2 Red + 2 White) configurations.
Three engineering parameters govern selection: (1) Calibration & Grade — Thermocouple Grade alloys (such as Types K, J, T, E and N) hold tight metallurgical accuracy near high-temperature junctions; Extension Grade cables (KX, JX, TX, EX, NX) use matching nominal alloys for economical routing up to ~200°C; and Compensating Grade cables (such as RCA/RCB, SCA/SCB and KCA/KCB) use cost-effective alternative alloys calibrated to replicate noble-metal or base-metal EMF curves across ambient runs; (2) Tolerance Class — IEC 60584-3 Class 1 and Class 2 align closely with ASTM E230 Special and Standard Limits of Error; and (3) Polarity Colour Code — IEC 60584-3 always codes the negative leg White, whereas ASTM E230 / ANSI MC96.1 always codes the negative leg Red. Never mix IEC and ANSI colour standards within the same plant loop.
CASMO manufactures thermocouple and RTD cables across a full spectrum of insulation, shielding and armouring tiers — spanning PVC (−20°C to +105°C), Silicone Rubber (to +180°C), FEP (to +200°C), PFA and ultra-thin Polyimide / Kapton® film (−190°C to +260°C), Fiberglass and PTFE-fiberglass composites (to +480°C), Mica + Fiberglass (to +600°C), and High Silica or Quartz fibre braids (+700°C to +1200°C), with stainless-steel mechanical overbraids and tinned-copper EMI shields.
Kapton® is a registered trademark of DuPont de Nemours, Inc.; CASMO CABLE LLC is an independent manufacturer not affiliated with or endorsed by DuPont. Confirm tolerance class, colour-code standard (IEC vs. ANSI) and temperature ceiling against CASMO's specification sheet prior to installation.
Related Standards, Materials & Applications
Frequently Asked Questions
- What is the difference between Thermocouple Grade, Extension Grade and Compensating Grade wire?
- Thermocouple Grade wire (Types K, J, T, E, N) uses high-purity matched alloys suitable for forming sensing junctions or routing near elevated heat. Extension Grade (KX, JX, TX, EX, NX) uses matching nominal alloys at lower cost for runs from the sensor head to instrumentation (typically −25°C to +200°C). Compensating Grade (KCA/KCB, RCA/RCB, SCA/SCB) uses alternative copper/nickel alloys calibrated to replicate Type K or noble-metal R/S EMF curves over ambient routing.
- Why must IEC 60584-3 and ASTM E230 / ANSI MC96.1 colour codes never be mixed?
- IEC 60584-3 assigns White to the negative conductor and uses Green for Type K, Black for Type J, Brown for Type T and Orange for Type R/S. ASTM E230 / ANSI MC96.1 assigns Red to the negative conductor and uses Yellow for Type K, White/Black for Type J, Blue for Type T and Green for Type R/S. Mixing conventions reverses polarity or misidentifies calibrations, introducing severe measurement error.
- How do IEC 60584-3 tolerance classes compare with ASTM E230 limits of error?
- IEC 60584-3 Class 1 (tighter tolerance, such as ±1.5°C for KX/JX/EX and ±0.5°C for TX from −25°C to +200°C) corresponds functionally to ASTM E230 Special Limits of Error, while IEC Class 2 (±2.5°C for KX/JX/EX and ±1.0°C for TX) corresponds to Standard Limits of Error.
- How do I choose insulation materials across the −190°C to +1200°C temperature range?
- Select PVC for economical ambient runs to 105°C; Silicone Rubber for flexible routing to 180°C; FEP (200°C), PFA (260°C) or Polyimide film (−190°C to +260°C) for chemical and moisture resistance; Fiberglass or PTFE-fiberglass composites up to 480°C; Mica + Fiberglass for 550°C–600°C; and High Silica or Quartz fibre braids for 700°C–1200°C furnace and turbine duty.
- When should I choose stainless-steel overbraiding versus an inner EMI shield?
- An outer stainless-steel braid protects against sharp edges, crush, abrasion and hot splatter in furnaces and test cells. An inner metallic shield beneath an extruded fluoropolymer jacket blocks VFD and motor EMI on microvolt signals while keeping the shield sealed against moisture and washdowns.
- Why do IEC 60751 PT100 RTD cables use 3-wire or 4-wire colour-coded conductors?
- Because RTDs measure resistance (100 Ω at 0°C for Pt100), lead resistance directly skews 2-wire readings. Under IEC 60751, Class A and Class AA accuracy require 3-wire (2 Red + 1 White) or 4-wire (2 Red + 2 White) cables so transmitters cancel lead resistance; same-colour leads connect to the same side of the platinum element.
Engineering Guides
- High-Temperature Conductor Selection (150°C to 1000°C+): Tin, Silver, 2% Nickel, 27% Nickel-Coated & Pure Nickel — Why copper oxidizes and forms brittle intermetallics at elevated temperatures — and how to match ASTM B33, B298, B355 (Class 2 & 27), and B160 conductor metallurgies to operating temperature, DCR voltage drop, and permanent termination methods.