IEC 60751 — Industrial Platinum RTD Sensor Cables
International standard for Pt100 and Pt1000 platinum resistance thermometers specifying Class AA/A/B tolerances and 2-, 3- and 4-wire Red/White lead colour coding.
Standard · International Electrotechnical Commission (IEC)
What is IEC 60751?
IEC 60751 (harmonised across Europe as EN 60751 / DIN EN 60751) defines temperature-resistance curves, tolerance classes (Class AA, A, B and C) and lead-wire identification for industrial platinum resistance thermometers such as Pt100 (100.00 Ω at 0°C) and Pt1000. Unlike thermocouples, RTDs do not require exotic thermoelectric alloys — extension cables use tightly matched tinned-copper or high-temperature nickel-plated copper conductors for balanced loop resistance.
Because lead resistance adds directly to 2-wire sensor readings, IEC 60751 requires 3-wire or 4-wire cable architectures for any tolerance tighter than Class B (including Class A and Class AA). Leads of the same colour terminate to the same electrical side of the platinum element: 3-wire cables use 2 Red + 1 White conductors, while 4-wire cables use 2 Red + 2 White conductors.
Key Technical Requirements
| Parameter | Requirement | Notes |
|---|---|---|
| Wiring systems | 3-wire (2 Red + 1 White) · 4-wire (2 Red + 2 White) | Same-colour leads share one side of the RTD element |
| Accuracy gating | Class A / AA require 3- or 4-wire cable | Eliminates lead-resistance measurement drift |
| Conductors | TPC (≤150°C–180°C) · SPC/2% NPC (200°C–260°C) · 27% NCC (≤480°C) | Matched core stranding for balanced loop resistance |
| Insulations | PVC · FEP · PFA · Fiberglass + optional shield | Stainless-steel or tinned-copper EMI protection |
Frequently Asked Questions
- Why do 3-core IEC 60751 RTD cables use 2 Red and 1 White conductors?
- Under IEC 60751, same-colour wires connect to the same terminal side of the Pt100 element, enabling the transmitter to measure and cancel lead-wire resistance automatically.
- When should I choose nickel-plated copper instead of tinned copper for RTD cables?
- Use tinned copper (ASTM B33) with PVC or lower-temperature runs up to +150°C–+180°C, upgrade to silver-plated (ASTM B298) or 2% nickel-plated copper (ASTM B355 Class 2) with FEP or PFA insulation for +200°C to +260°C service, and specify 27% nickel-coated copper (ASTM B355 Class 27) with fiberglass insulation for continuous high-heat zones up to +480°C.