TC-VV is a CASMO thermocouple wire for Thermocouple Wire. PVC insulated, -20°C to +105°C. 2-core parallel flat thermocouple and extension cable with extruded PVC core insulation and PVC outer jacket (-20°C to +105°C) per IEC 60584-3 and ASTM E230.
2-core parallel flat thermocouple and extension cable with extruded PVC core insulation and PVC outer jacket (-20°C to +105°C) per IEC 60584-3 and ASTM E230.
Key Ratings
- TC-VV: · Temperature -20°C to +105°C
Construction
- Conductor
- Thermocouple Alloy (Type K / J / T / E / N) or Extension / Compensating Alloy (Type KX / JX / TX / EX / NX / RX / SX) · Stranded
- Core Insulation
- Extruded · PVC
- Cabling
- Parallel · Duplex parallel flat core pair
- Core Identification
- Color-coded per IEC 60584-3 (Type K/KX: +Green / -White) or ASTM E230 on request
- Jacket
- Extruded · PVC
Characteristics
- Signal Circuit Duty: Low-voltage thermoelectric millivolt EMF measurement and extension signal circuits only (not rated for mains power distribution).
- Calibrated EMF Accuracy: Matched thermoelectric conductor pairs maintain stable electromotive force characteristics across the rated temperature span.
- Moisture Resistance: Resistant to moisture and humidity, helping maintain the integrity of the cable covering in damp environments.
- Oil Resistance: Resistant to oil exposure, helping maintain the integrity of the cable covering in oily environments.
- Flexibility: Flexible construction facilitates routing, bending and installation where space is limited.
Applications
- Process Temperature Sensing and Pyrometry: For connecting thermocouple probes and cold-junction transmitters across chemical, petrochemical, power-generation and metallurgical plants.
- Control Cabinets: For wiring within control cabinets, control panels and electrical assemblies.
- Sensors and Instrumentation: For connections between sensors, measuring instruments and associated control equipment.
Standards & Compliance
- Standard: IEC 60584-3 / ASTM E230
- RoHS: Compliant
- REACH: Compliant
TC-VV — PVC Insulated 105°C Duplex Thermocouple Wire
| CASMO Part No. | Total Cores | Conductor Size (AWG) | No. Of Strands | Nom. Strand Dia. (mm) | Nom. Conductor Dia. (mm) | Nom. Ins. Thickness (mm) | Nom. Core O.D. (mm) | Nom. Jkt. Thickness (mm) | Nom. Overall Width (mm) | Overall Width Tolerance ± (mm) | Nom. Overall Thickness (mm) | Overall Thickness Tolerance ± (mm) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 710012C26-KX-XX | 2 | 26 | 7 | 0.16 | 0.48 | 0.3 | 1.1 | 0.5 | 3.2 | 0.2 | 2.1 | 0.2 |
| 710012C24-KX-XX | 2 | 24 | 7 | 0.2 | 0.6 | 0.3 | 1.2 | 0.5 | 3.4 | 0.2 | 2.2 | 0.2 |
| 710012C22-KX-XX | 2 | 22 | 7 | 0.254 | 0.76 | 0.3 | 1.4 | 0.5 | 3.8 | 0.2 | 2.4 | 0.2 |
| 710012C20-KX-XX | 2 | 20 | 7 | 0.32 | 0.96 | 0.3 | 1.6 | 0.5 | 4.2 | 0.2 | 2.6 | 0.2 |
| 710012C18-KX-XX | 2 | 18 | 7 | 0.39 | 1.17 | 0.4 | 2.0 | 0.6 | 5.2 | 0.2 | 3.2 | 0.2 |
| 710012C16-KX-XX | 2 | 16 | 19 | 0.3 | 1.5 | 0.4 | 2.3 | 0.6 | 5.8 | 0.2 | 3.5 | 0.2 |
| 710012C14-KX-XX | 2 | 14 | 19 | 0.37 | 1.85 | 0.4 | 2.7 | 0.6 | 6.6 | 0.2 | 3.9 | 0.2 |
* "-KX-" = Type KX extension-grade alloy pair (NiCr / NiAl, standard; EMF calibrated up to +200°C). Substitute "-JX-", "-EX-", "-NX-", "-RX-", "-SX-" (EMF calibrated ≤ +200°C), "-TX-" (EMF calibrated ≤ +100°C), or thermocouple-grade "-K-", "-J-", "-T-", "-E-", "-N-" for sensing-junction service (Type T wire-gauge limit: +200°C for 26–20 AWG). † "-XX" = color-code suffix: IEC 60584-3 color code supplied as standard (e.g., GN for Type K/KX); ASTM E230 color code available upon request (see Color Code Chart below).
- "-KX-" = Type KX extension-grade alloy pair (NiCr / NiAl, standard; EMF calibrated up to +200°C). Substitute "-JX-", "-EX-", "-NX-", "-RX-", "-SX-" (EMF calibrated ≤ +200°C), "-TX-" (EMF calibrated ≤ +100°C), or thermocouple-grade "-K-", "-J-", "-T-", "-E-", "-N-" for sensing-junction service (Type T wire-gauge limit: +200°C for 26–20 AWG).
- "-XX" = color-code suffix: IEC 60584-3 color code supplied as standard (e.g., GN for Type K/KX); ASTM E230 color code available upon request (see Color Code Chart below).
Color Code Chart
- +Green / -White (Jkt: Green)
- +Black / -White (Jkt: Black)
- +Brown / -White (Jkt: Brown; TX ≤100°C)
- +Violet / -White (Jkt: Violet)
- +Pink / -White (Jkt: Pink)
- +Orange / -White (Jkt: Orange; ≤100°C)
- +Yellow / -Red (TC: Brown / Ext: Yellow)
- +White / -Red (TC: Brown / Ext: Black)
- +Blue / -Red (TC: Brown / Ext: Blue; TX ≤100°C)
- +Purple / -Red (TC: Brown / Ext: Purple)
- +Orange / -Red (TC: Brown / Ext: Orange)
- +Black / -Red (Ext: Green; ≤200°C)