TYPE W SINGLE-CONDUCTOR
TYPE W SINGLE-CONDUCTOR is a CASMO flexible cord for Flexible Cords. EPDM insulated, -40°C to +90°C, 2000V. Type W single-conductor portable power cable constructed in accordance with UL 1650 (−40°C to +90°C wet and dry, 2000V AC) with extra-flexible bare copper conductor, PET separator, thermose…
Type W single-conductor portable power cable constructed in accordance with UL 1650 (−40°C to +90°C wet and dry, 2000V AC) with extra-flexible bare copper conductor, PET separator, thermoset EPDM insulation and heavy-duty oil- and weather-resistant CPE outer jacket.
Key Ratings
- TYPE W SINGLE-CONDUCTOR: · Temperature -40°C to +90°C · Rated Voltage 2000V
Construction
- Conductor
- Bare Copper · Extra-Flexible Stranded
- Separator
- PET tape over conductor
- Insulation
- Extruded · EPDM
- Jacket
- CPE · Extruded
Characteristics
- Wet & Dry Rating: 90°C continuous wet and dry
- Oil Immersion Rating: 75°C (60 days immersion; ≥ 65% tensile and elongation retention)
- Cold Bend: −40°C × 4 h, no cracking
- Spark Test Voltage: 10 kV (12–2 AWG); 13 kV (1–4/0 AWG); 15 kV (250–500 kcmil)
- Dielectric Withstand Voltage (1 min): 3 kV (12–10 AWG); 4 kV (8–2 AWG); 5 kV (1–4/0 AWG); 6 kV (250–500 kcmil)
- Oil Resistance: Resistant to oil exposure, helping maintain the integrity of the cable covering in oily environments.
- Weather Resistance: Resistant to weathering, helping maintain cable integrity under exposure to sunlight, moisture and changing weather conditions.
- Abrasion Resistance: Resistant to abrasion, helping protect the cable surface against wear caused by rubbing and handling.
- Low-Temperature Flexibility: Maintains flexibility at low temperatures, facilitating cable routing and handling in cold environments.
Applications
- Portable Tools and Industrial Equipment: For portable power tools, mobile machinery and temporary industrial power connections, subject to the applicable service cord rating and installation conditions.
- Industrial Automation: For power, signal or control connections within industrial automation systems, as specified for the selected cable construction.
- Heavy-Duty Temporary Power Distribution: For mobile generators, power feeders, stage and industrial distribution boxes, motor leads and rugged wet-location equipment connections rated up to 2000V AC.
Standards & Compliance
- Standard: UL 1650
- Fire Performance: FT1, FT5
- RoHS: Compliant
- REACH: Compliant
Single-Conductor (1C)
| CASMO Part No. | Conductor Size (AWG) | No. Of Strands | Nom. Strand Dia. (mm) | Nom. Conductor Dia. (mm) | Nom. Ins. Thickness (mm) | Min. Ins. Thickness (mm) | Nom. Jkt. Thickness (mm) | Min. Jkt. Thickness (mm) | Nom. O.D. (mm) | O.D. Tolerance ± (mm) | Max. DCR @20°C (Ω/km) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1114211C12 | 12 | 65 | 0.254 | 2.40 | 1.52 | 1.37 | 1.91 | 1.53 | 9.6 | 0.5 | 5.43 |
| 1114211C10 | 10 | 105 | 0.254 | 3.00 | 1.52 | 1.37 | 1.91 | 1.53 | 10.3 | 0.5 | 3.41 |
| 1114211C8 | 8 | 168 | 0.254 | 3.90 | 1.52 | 1.37 | 1.91 | 1.53 | 11.4 | 0.6 | 2.18 |
| 1114211C6 | 6 | 266 | 0.254 | 4.90 | 1.52 | 1.37 | 2.41 | 1.93 | 13.4 | 0.6 | 1.38 |
| 1114211C4 | 4 | 427 | 0.254 | 6.30 | 1.52 | 1.37 | 2.41 | 1.93 | 14.7 | 0.6 | 0.865 |
| 1114211C3 | 3 | 532 | 0.254 | 7.00 | 1.52 | 1.37 | 2.41 | 1.93 | 15.4 | 0.6 | 0.693 |
| 1114211C2 | 2 | 665 | 0.254 | 7.90 | 1.52 | 1.37 | 2.41 | 1.93 | 16.4 | 0.8 | 0.549 |
| 1114211C1 | 1 | 855 | 0.254 | 9.10 | 2.03 | 1.83 | 2.41 | 1.93 | 18.5 | 0.8 | 0.436 |
| 1114211C1_0 | 1/0 | 1045 | 0.254 | 10.20 | 2.03 | 1.83 | 2.41 | 1.93 | 19.5 | 1.0 | 0.345 |
| 1114211C2_0 | 2/0 | 1330 | 0.254 | 11.50 | 2.03 | 1.83 | 2.41 | 1.93 | 20.9 | 1.0 | 0.273 |
| 1114211C3_0 | 3/0 | 1672 | 0.254 | 12.80 | 2.03 | 1.83 | 2.41 | 1.93 | 22.1 | 1.0 | 0.217 |
| 1114211C4_0 | 4/0 | 2109 | 0.254 | 14.40 | 2.03 | 1.83 | 2.41 | 1.93 | 23.7 | 1.0 | 0.172 |
| 1114211C250MCM | 250 kcmil | 2516 | 0.254 | 15.60 | 2.41 | 2.17 | 2.41 | 1.93 | 25.7 | 1.2 | 0.147 |
| 1114211C350MCM | 350 kcmil | 3478 | 0.254 | 18.40 | 2.41 | 2.17 | 2.41 | 1.93 | 28.4 | 1.2 | 0.105 |
| 1114211C500MCM | 500 kcmil | 1225 | 0.511 | 21.90 | 2.41 | 2.17 | 2.41 | 1.93 | 31.9 | 1.5 | 0.0735 |
* Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard core insulation color is White under a Black CPE outer jacket. † UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.
- Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard core insulation color is White under a Black CPE outer jacket.
- UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.