BUS CAN

BUS CAN is a CASMO industrial fieldbus cable for Industrial Fieldbus. Foam PE insulated, -40°C to +80°C, 250V. 120 Ω shielded twisted-pair industrial CAN, CANopen and CAN FD physical-layer bus cable with low-capacitance cellular PE insulation and flame-retardant violet PVC sheath for fixed instal…

120 Ω shielded twisted-pair industrial CAN, CANopen and CAN FD physical-layer bus cable with low-capacitance cellular PE insulation and flame-retardant violet PVC sheath for fixed installations.

Key Ratings

  • BUS CAN: · Temperature -40°C to +80°C · Rated Voltage 250V · Test Voltage 1500V

Construction

Conductor
Bare Copper · Stranded
Core Insulation
Foamed · Foam PE
Cabling
Twisted
Core Identification
1×2: White / Brown; 2×2: White / Brown, Green / Yellow (DIN 47100)
Shield
Braid · Tinned copper braid
Jacket
Extruded · PVC

Characteristics

  • Occasional Flexing Temperature: -5°C to +70°C
  • Characteristic Impedance: 120 Ω ± 12 Ω (at 1 MHz)
  • Mutual Capacitance: Approx. 40 nF/km (at 800 Hz)
  • Velocity of Propagation: Approx. 76%
  • Low-Capacitance Signal Integrity: Low-capacitance insulation and balanced pair twist help limit signal attenuation across extended transmission distances.
  • EMC Interference Shielding: Metallic shielding helps suppress electromagnetic interference and maintain signal integrity in electrically noisy environments.
  • Flexibility: Flexible construction facilitates routing, bending and installation where space is limited.

Applications

  • Fieldbus and Serial Data Networks: For differential serial and fieldbus communication links between programmable controllers, distributed I/O modules, drives and field devices.
  • Control Cabinets: For wiring within control cabinets, control panels and electrical assemblies.

Standards & Compliance

  • Standard: ISO 11898-2
  • Fire Performance: IEC 60332-1-2
  • RoHS: Compliant
  • REACH: Compliant

Specification Data

CASMO Part No.Conductor Size (mm²)No. Of StrandsNom. Strand Dia. (mm)Nom. Ins. Thickness (mm)Nom. Core O.D. (mm)Min. Braid Coverage (%)Nom. Jkt. Thickness (mm)Nom. O.D. (mm)Max. DCR @20°C (Ω/km)
1230010.22/7-1P-AS-VT1×2×0.2270.200.521.65800.855.793.0
1230010.22/7-2P-AS-VT2×2×0.2270.200.521.65800.957.393.0
1230010.34/7-1P-AS-VT1×2×0.3470.250.622.00800.956.857.5
1230010.34/7-2P-AS-VT2×2×0.3470.250.622.00801.108.457.5
1230010.5/7-1P-AS-VT1×2×0.570.300.752.40801.057.839.0
1230010.5/7-2P-AS-VT2×2×0.570.300.752.40801.209.739.0
1230010.75/19-1P-AS-VT1×2×0.75190.230.852.85801.108.726.0

* "-AS-" = stranded bare copper conductor; "-1P" / "-2P" = number of twisted pairs; "-VT" = violet (RAL 4001) PVC outer sheath (standard). † Max. DCR @20°C is specified per single conductor; maximum DC loop resistance equals 2 × single-conductor DCR (186 / 115 / 78 / 52 Ω/km for 0.22 / 0.34 / 0.5 / 0.75 mm²).

  • "-AS-" = stranded bare copper conductor; "-1P" / "-2P" = number of twisted pairs; "-VT" = violet (RAL 4001) PVC outer sheath (standard).
  • Max. DCR @20°C is specified per single conductor; maximum DC loop resistance equals 2 × single-conductor DCR (186 / 115 / 78 / 52 Ω/km for 0.22 / 0.34 / 0.5 / 0.75 mm²).

Related Categories