RTD-FPF

RTD-FPF is a CASMO rtd cable for RTD / PT100 Cable. FEP insulated, -65°C to +200°C. 3-core stranded silver-plated copper RTD / PT100 cable with extruded FEP cores, internal silver-plated copper braid EMI shield, and sealed FEP outer jacket (-65°C to +200°C).

3-core stranded silver-plated copper RTD / PT100 cable with extruded FEP cores, internal silver-plated copper braid EMI shield, and sealed FEP outer jacket (-65°C to +200°C).

Key Ratings

  • RTD-FPF: · Temperature -65°C to +200°C

Construction

Conductor
Silver Plated Copper or Nickel Plated Copper · Stranded
Core Insulation
Extruded · FEP
Cabling
Laid Up · 3-core concentric twist
Core Identification
3-wire IEC 60751 color code (2 Red + 1 White)
Shield
Braid · Silver-plated copper braid (≥85%)
Jacket
Extruded · FEP

Characteristics

  • Signal Circuit Duty: Low-voltage RTD excitation and bridge measurement signal circuits only (not rated for mains power distribution); extruded core insulation is factory dielectric-verified at 1000 V AC for 1 min.
  • Low-Resistance Lead Compensation: Matched three-conductor copper construction minimizes lead-wire resistance imbalance in bridge-connected RTD circuits.
  • EMC Interference Shielding: Metallic shielding helps suppress electromagnetic interference and maintain signal integrity in electrically noisy environments.
  • Chemical Resistance: Resistant to chemical exposure, helping protect the cable covering against deterioration in chemically demanding environments.
  • Moisture Resistance: Resistant to moisture and humidity, helping maintain the integrity of the cable covering in damp environments.

Applications

  • PT100 and RTD Resistance Thermometry: For three-wire resistance thermometer lead connections between RTD sensors, transmitters and temperature controllers.
  • Autoclaves, Cryogenic Chambers and Test Rigs: For precision thermal profiling in aerospace autoclaves, environmental test chambers, semiconductor tools and laboratory instrumentation.
  • Sensors and Instrumentation: For connections between sensors, measuring instruments and associated control equipment.

Standards & Compliance

  • Standard: IEC 60751
  • RoHS: Compliant
  • REACH: Compliant

RTD-FPF — 3-Core FEP Insulated, SPC Shielded & FEP 200°C RTD Cable

CASMO Part No.Total CoresConductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Conductor Dia. (mm)Nom. Ins. Thickness (mm)Nom. Core O.D. (mm)Nom. Shield Thickness (mm)Nom. Jkt. Thickness (mm)Nom. O.D. (mm)O.D. Tolerance ± (mm)
710373C26-SS-XX32670.160.480.20.90.20.53.30.2
710373C24-SS-XX32470.20.60.21.00.20.53.60.2
710373C22-SS-XX32270.2540.760.21.20.20.54.00.2
710373C20-SS-XX32070.320.960.21.40.20.54.40.2
710373C18-SS-XX31870.391.170.251.70.20.55.10.3
710373C16-SS-XX316190.31.50.252.00.20.55.70.3
710373C14-SS-XX314190.371.850.252.40.20.56.60.3

* "-SS-" = stranded silver-plated copper conductor with silver-plated copper braid EMI shield (standard for 200°C FEP RTD cable; "-NS-" 2% nickel-plated copper optional). Standard 3-core IEC 60751 configuration (2 Red + 1 White); 2-core (2C) and 4-core (4C) constructions available upon request. † "-XX" = outer jacket color code: RD Red (standard), WH White, BK Black, or GY Grey (3-core identification per Color Code Chart below).

  • "-SS-" = stranded silver-plated copper conductor with silver-plated copper braid EMI shield (standard for 200°C FEP RTD cable; "-NS-" 2% nickel-plated copper optional). Standard 3-core IEC 60751 configuration (2 Red + 1 White); 2-core (2C) and 4-core (4C) constructions available upon request.
  • "-XX" = outer jacket color code: RD Red (standard), WH White, BK Black, or GY Grey (3-core identification per Color Code Chart below).

Color Code Chart

  • Red (Lead A)
  • Red (Lead A')
  • White (Sense B)

Related Categories