SOOW / H07RN-F

SOOW / H07RN-F is a CASMO flexible cord for Flexible Cords. EPR (EPDM) insulated, -40°C to +90°C, 600V. SOOW / H07RN-F dual-standard extra-hard-service rubber portable cord constructed in accordance with UL 62 / CSA C22.2 No. 49 and EN 50525-2-21 / IEC 60245-4, built with flexible Class 5 bare co…

SOOW / H07RN-F dual-standard extra-hard-service rubber portable cord constructed in accordance with UL 62 / CSA C22.2 No. 49 and EN 50525-2-21 / IEC 60245-4, built with flexible Class 5 bare copper conductors, oil-resistant thermoset EPR (EPDM) insulation and heavy-duty oil-, UV- and weather-resistant CPE thermoset jacket.

Key Ratings

  • SOOW / H07RN-F: · Temperature -40°C to +90°C · Rated Voltage 600V · Test Voltage 2500V / 5 min

Construction

Conductor
Bare Copper · Flexible Stranded
Core Insulation
Extruded · EPR (EPDM)
Cabling
Laid Up · Separator tape wrapped over laid-up cores; fillers and separator tapes applied as required for circularity.
Core Identification
Color-coded per HD 308 S2 (see Color Code Chart)
Jacket
Extruded · CPE

Characteristics

  • H07RN-F Temperature Range: -25°C to +60°C (flexing) and -40°C to +60°C (fixed); up to +85°C ambient (+90°C max. conductor) in fixed protected installations.
  • H07RN-F Rated Voltage: 450/750V AC (up to 600/1000V AC in fixed protected installations).
  • Oil Resistance: Resistant to oil exposure, helping maintain the integrity of the cable covering in oily environments.
  • Weather Resistance: Resistant to weathering, helping maintain cable integrity under exposure to sunlight, moisture and changing weather conditions.
  • Extra-Hard Service Durability: Heavy-duty elastomer construction withstands abrasion, crushing, impact and rough portable handling on industrial sites.
  • Low-Temperature Flexibility: Maintains flexibility at low temperatures, facilitating cable routing, coiling and handling in cold environments.

Applications

  • Global Export Machinery & Industrial Equipment: Dual-standard power supply and control cord for industrial machinery and equipment exported to both North American (UL 62 / CSA C22.2 No. 49) and European (EN 50525-2-21) markets without rewiring.
  • Industrial Portable Power & Temporary Distribution: Extra-hard-usage portable power connections for heavy tools, cranes, hoists, portable lights, mobile generators and outdoor wet locations; use as permitted by NEC Article 400 and EN 50565-2.

Standards & Compliance

  • Standard: UL 62 / EN 50525-2-21
  • Fire Performance: FT2, IEC 60332-1-2
  • RoHS: Compliant
  • REACH: Compliant

SOOW / H07RN-F

CASMO Part No.Conductor Size (AWG)Nom. SizeNo. Of StrandsNom. Strand Dia. (mm)Min. Ins. Thickness (mm)Min. Jkt. Thickness (mm)Min. Overall O.D. (mm)Max. Overall O.D. (mm)Max. DCR @20°C (Ω/km)Nom. Cable Weight (kg/km)
1114202C1717/22×1.0 mm²330.200.691.228.899.9117.6112
1114203C1717/33G1.0 mm²330.200.691.229.5010.2017.6125
1114204C1717/44G1.0 mm²330.200.691.2210.1611.3017.6147
1114205C1717/55G1.0 mm²330.200.691.6311.8113.1017.6207
1114202C1515/22×1.5 mm²330.250.691.229.6010.7011.1137
1114203C1515/33G1.5 mm²330.250.691.2610.3011.4011.1163
1114204C1515/44G1.5 mm²330.250.691.3511.3012.6011.1197
1114205C1515/55G1.5 mm²330.250.691.6312.9014.2011.1261
1114203C1313/33G2.5 mm²530.251.021.6313.2114.006.98266
1114204C1313/44G2.5 mm²530.251.021.6314.6015.506.98328
1114203C1111/33G4 mm²580.301.021.9315.5016.204.39377
1114204C1111/44G4 mm²580.301.021.9316.7017.904.39456
1114205C1111/55G4 mm²580.301.021.9318.3019.904.39548
1114203C99/33G6 mm²930.301.021.9317.0018.002.79487
1114204C99/44G6 mm²930.301.021.9318.4020.002.79587
1114203C77/33G10 mm²830.401.372.7123.0024.201.75852
1114204C77/44G10 mm²830.401.372.7925.1026.501.751050
1114203C55/33G16 mm²1330.401.372.8826.7027.601.101188
1114204C55/44G16 mm²1330.401.372.9629.2030.101.101467
1114203C33/33G25 mm²2100.401.373.1531.0033.000.6941689
1114204C33/44G25 mm²2100.401.373.4533.8036.600.6942103

1 Standard jacket color: Black. Core color identification follows UL 62 international code (Light Blue ground-referenced conductor; G/Y = Green/Yellow protective earth, 50%–70% Green / 30%–50% Yellow) and European HD 308 S2 (see Color Code Chart below). In European size designations, "G" indicates a cable with a Green/Yellow protective earth (ground) conductor, while "×" indicates without a protective earth conductor. 2 Minimum point insulation and jacket walls reflect the stricter requirement of UL 62 and EN 50525-2-21; mean (average) wall thicknesses simultaneously meet or exceed both UL 62 minimum average thickness and EN 50525-2-21 Table B.2 nominal values. 3 Max. DC resistance at 20°C satisfies the stricter UL 62 Table 4 multiconductor cord limit (including 2% lay allowance), simultaneously meeting IEC 60228 Class 5 with margin.

  • Standard jacket color: Black. Core color identification follows UL 62 international code (Light Blue ground-referenced conductor; G/Y = Green/Yellow protective earth, 50%–70% Green / 30%–50% Yellow) and European HD 308 S2 (see Color Code Chart below). In European size designations, "G" indicates a cable with a Green/Yellow protective earth (ground) conductor, while "×" indicates without a protective earth conductor.
  • Minimum point insulation and jacket walls reflect the stricter requirement of UL 62 and EN 50525-2-21; mean (average) wall thicknesses simultaneously meet or exceed both UL 62 minimum average thickness and EN 50525-2-21 Table B.2 nominal values.
  • Max. DC resistance at 20°C satisfies the stricter UL 62 Table 4 multiconductor cord limit (including 2% lay allowance), simultaneously meeting IEC 60228 Class 5 with margin.

Color Code Chart

  • Brown, Light Blue
  • G/Y, Brown, Light Blue
  • G/Y, Brown, Black, Grey
  • G/Y, Light Blue, Brown, Black, Grey