TYPE W MULTI-CONDUCTOR

TYPE W MULTI-CONDUCTOR is a CASMO flexible cord for Flexible Cords. EPDM insulated, -40°C to +90°C, 2000V. Type W multi-conductor (2C–5C) portable power cable constructed in accordance with UL 1650 (−40°C to +90°C wet and dry, 2000V AC) with extra-flexible bare copper conductors, PET separator, c…

Type W multi-conductor (2C–5C) portable power cable constructed in accordance with UL 1650 (−40°C to +90°C wet and dry, 2000V AC) with extra-flexible bare copper conductors, PET separator, color-coded thermoset EPDM insulation and heavy-duty oil- and weather-resistant CPE outer jacket.

Key Ratings

  • TYPE W MULTI-CONDUCTOR: · Temperature -40°C to +90°C · Rated Voltage 2000V

Construction

Conductor
Bare Copper · Extra-Flexible Stranded
Separator
PET tape over conductor
Core Insulation
Extruded · EPDM
Cabling
Laid Up
Core Identification
Color-coded per Color Code Chart
Filler
Cotton yarn (12–10 AWG); Rubber strip as required (≥ 8 AWG)
Binder
Non-woven tape
Jacket
Extruded · CPE

Characteristics

  • Wet & Dry Rating: 90°C continuous wet and dry
  • Oil Immersion Rating: 75°C (60 days immersion; ≥ 65% tensile and elongation retention)
  • Cold Bend: −40°C × 4 h, no cracking
  • Spark Test Voltage: 10 kV (12–2 AWG); 13 kV (1–4/0 AWG); 15 kV (250–500 kcmil)
  • Dielectric Withstand Voltage (1 min): 3 kV (12–10 AWG); 4 kV (8–2 AWG); 5 kV (1–4/0 AWG); 6 kV (250–500 kcmil)
  • Oil Resistance: Resistant to oil exposure, helping maintain the integrity of the cable covering in oily environments.
  • Weather Resistance: Resistant to weathering, helping maintain cable integrity under exposure to sunlight, moisture and changing weather conditions.
  • Abrasion Resistance: Resistant to abrasion, helping protect the cable surface against wear caused by rubbing and handling.
  • Low-Temperature Flexibility: Maintains flexibility at low temperatures, facilitating cable routing and handling in cold environments.

Applications

  • Portable Tools and Industrial Equipment: For portable power tools, mobile machinery and temporary industrial power connections, subject to the applicable service cord rating and installation conditions.
  • Industrial Automation: For power, signal or control connections within industrial automation systems, as specified for the selected cable construction.
  • Heavy-Duty Temporary Power Distribution: For mobile generators, power feeders, stage and industrial distribution boxes, motor leads and rugged wet-location equipment connections rated up to 2000V AC.

Standards & Compliance

  • Standard: UL 1650
  • Fire Performance: FT1, FT5
  • RoHS: Compliant
  • REACH: Compliant

2-Conductor (2C)

CASMO Part No.Conductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Conductor Dia. (mm)Nom. Ins. Thickness (mm)Min. Ins. Thickness (mm)Nom. Jkt. Thickness (mm)Min. Jkt. Thickness (mm)Nom. O.D. (mm)O.D. Tolerance ± (mm)Max. DCR @20°C (Ω/km)
1114212C122×12650.2542.401.521.371.911.5315.20.85.43
1114212C102×101050.2543.001.521.371.911.5316.60.83.41
1114212C82×81680.2543.901.521.372.772.2220.21.22.18
1114212C62×62660.2544.901.521.372.772.2222.21.21.38
1114212C42×44270.2546.301.521.372.772.2225.01.20.865
1114212C32×35320.2547.001.521.372.772.2226.41.20.693
1114212C22×26650.2547.901.521.373.582.8630.01.50.549
1114212C12×18550.2549.102.031.833.963.1734.91.50.436
1114212C1_02×1/010450.25410.202.031.833.963.1736.81.50.345
1114212C2_02×2/013300.25411.502.031.833.963.1739.61.50.273
1114212C3_02×3/016720.25412.802.031.833.963.1741.92.00.217
1114212C4_02×4/021090.25414.402.031.834.373.5045.92.00.172
1114212C250MCM2×250 kcmil25160.25415.602.412.174.833.8650.82.50.147
1114212C350MCM2×350 kcmil34780.25418.402.412.175.084.0656.73.00.105
1114212C500MCM2×500 kcmil12250.51121.902.412.175.084.0663.63.00.0735

* Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below. † UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

  • Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below.
  • UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

3-Conductor (3C)

CASMO Part No.Conductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Conductor Dia. (mm)Nom. Ins. Thickness (mm)Min. Ins. Thickness (mm)Nom. Jkt. Thickness (mm)Min. Jkt. Thickness (mm)Nom. O.D. (mm)O.D. Tolerance ± (mm)Max. DCR @20°C (Ω/km)
1114213C123×12650.2542.401.521.371.911.5316.10.85.43
1114213C103×101050.2543.001.521.371.911.5317.60.83.41
1114213C83×81680.2543.901.521.373.582.8623.01.22.18
1114213C63×62660.2544.901.521.373.582.8625.11.21.38
1114213C43×44270.2546.301.521.373.582.8628.21.50.865
1114213C33×35320.2547.001.521.373.582.8629.71.50.693
1114213C23×26650.2547.901.521.373.582.8631.81.50.549
1114213C13×18550.2549.102.031.833.582.8636.21.50.436
1114213C1_03×1/010450.25410.202.031.833.963.1739.02.00.345
1114213C2_03×2/013300.25411.502.031.833.963.1742.02.00.273
1114213C3_03×3/016720.25412.802.031.833.963.1744.52.00.217
1114213C4_03×4/021090.25414.402.031.834.373.5048.72.00.172
1114213C250MCM3×250 kcmil25160.25415.602.412.176.104.8856.43.00.147
1114213C350MCM3×350 kcmil34780.25418.402.412.176.104.8862.33.00.105
1114213C500MCM3×500 kcmil12250.51121.902.412.176.865.4971.23.00.0735

* Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below. † UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

  • Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below.
  • UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

4-Conductor (4C)

CASMO Part No.Conductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Conductor Dia. (mm)Nom. Ins. Thickness (mm)Min. Ins. Thickness (mm)Nom. Jkt. Thickness (mm)Min. Jkt. Thickness (mm)Nom. O.D. (mm)O.D. Tolerance ± (mm)Max. DCR @20°C (Ω/km)
1114214C124×12650.2542.401.521.371.911.5317.50.85.43
1114214C104×101050.2543.001.521.371.911.5319.20.83.41
1114214C84×81680.2543.901.521.373.582.8624.71.22.18
1114214C64×62660.2544.901.521.373.582.8627.31.21.38
1114214C44×44270.2546.301.521.373.582.8630.61.50.865
1114214C34×35320.2547.001.521.373.582.8632.31.50.693
1114214C24×26650.2547.901.521.373.963.1735.41.50.549
1114214C14×18550.2549.102.031.833.963.1740.41.50.436
1114214C1_04×1/010450.25410.202.031.833.963.1742.72.00.345
1114214C2_04×2/013300.25411.502.031.833.963.1746.02.00.273
1114214C3_04×3/016720.25412.802.031.833.963.1748.92.00.217
1114214C4_04×4/021090.25414.402.031.835.204.1655.13.00.172
1114214C250MCM4×250 kcmil25160.25415.602.412.176.865.4963.23.00.147
1114214C350MCM4×350 kcmil34780.25418.402.412.176.865.4969.83.00.105
1114214C500MCM4×500 kcmil12250.51121.902.412.177.876.3080.14.00.0735

* Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below. † UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

  • Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below.
  • UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

5-Conductor (5C)

CASMO Part No.Conductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Conductor Dia. (mm)Nom. Ins. Thickness (mm)Min. Ins. Thickness (mm)Nom. Jkt. Thickness (mm)Min. Jkt. Thickness (mm)Nom. O.D. (mm)O.D. Tolerance ± (mm)Max. DCR @20°C (Ω/km)
1114215C125×12650.2542.401.521.371.911.5319.11.05.43
1114215C105×101050.2543.001.521.371.911.5321.01.03.41
1114215C85×81680.2543.901.521.373.562.8526.71.22.18
1114215C65×62660.2544.901.521.373.562.8529.51.21.38
1114215C45×44270.2546.301.521.373.943.1534.11.50.865
1114215C35×35320.2547.001.521.373.943.1535.91.50.693
1114215C25×26650.2547.901.521.374.323.4639.31.50.549
1114215C15×18550.2549.102.031.835.204.1646.62.00.436
1114215C1_05×1/010450.25410.202.031.835.204.1649.32.00.345
1114215C2_05×2/013300.25411.502.031.835.204.1653.03.00.273
1114215C3_05×3/016720.25412.802.031.835.204.1656.13.00.217
1114215C4_05×4/021090.25414.402.031.835.594.4761.23.00.172

* Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below. † UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

  • Bare annealed copper stranding per ASTM B172: Class K for 12 AWG–350 kcmil and Class I for 500 kcmil. Standard outer jacket color is Black; core identification follows the Color Code Chart below.
  • UL 1650 Type W Listing covers 8 AWG through 500 kcmil; 12 AWG and 10 AWG are constructed to equivalent Type W dimensional and performance guidelines.

Color Code Chart

  • Black, White
  • Black, White, Green
  • Black, White, Red, Green
  • Black, White, Red, Orange, Green