UL 20668 SHIELDED TP

UL 20668 SHIELDED TP is a CASMO control & data cable for Control & Data Cable. SR-PVC insulated, -30°C to +90°C, 300V. UL 758 AWM Style 20668 twisted-pair 90°C industrial instrumentation cable with overall 100% aluminum/polyester (Al/PET) foil + ≥85% tinned-copper braid shield, SR-PVC insulation …

UL 758 AWM Style 20668 twisted-pair 90°C industrial instrumentation cable with overall 100% aluminum/polyester (Al/PET) foil + ≥85% tinned-copper braid shield, SR-PVC insulation and PUR/TPU jacket (-30°C to +90°C, 300V AC).

Key Ratings

  • UL 20668 SHIELDED TP: · Temperature -30°C to +90°C · Rated Voltage 300V · Test Voltage 2000V / 1 min

Construction

Conductor
Tinned Copper · Stranded
Core Insulation
Extruded · SR-PVC
Cabling
Twisted · Cores twisted into pairs, pairs cabled together
Core Identification
Color-coded twisted pairs per Standard Paired Color Chart (Chart A)
Binder
Non-woven tape
Shield
Foil Braid · Aluminum/polyester (Al/PET) foil (100%) + Tinned Copper Braid (≥85%)
Drain Wire
Stranded Tinned Copper Drain Wire
Jacket
Extruded (Matte Black standard) · PUR/TPU

Characteristics

  • Occasional Flexing Temperature: -5°C to +80°C
  • Oil Resistance: Resistant to oil exposure, helping maintain the integrity of the cable covering in oily environments.
  • Abrasion Resistance: Resistant to abrasion, helping protect the cable surface against wear caused by rubbing and handling.
  • Mechanical Strength: Provides mechanical strength to withstand handling and installation stresses and help maintain cable integrity.
  • Flexibility: Flexible construction facilitates routing, bending and installation where space is limited.
  • EMI / RFI Shielding: 100% aluminum/polyester (Al/PET) foil plus ≥85% tinned-copper braid shield provides broadband EMI/RFI protection in electrically noisy automation environments.

Applications

  • Sensors and Instrumentation: For connections between sensors, measuring instruments and associated control equipment.
  • Industrial Automation: For power, signal or control connections within industrial automation systems, as specified for the selected cable construction.

Standards & Compliance

  • Standard: UL 758 AWM
  • Fire Performance: VW-1, FT1, FT2
  • RoHS: Compliant
  • REACH: Compliant

UL 20668 SHIELDED TP — Foil + Braid Shielded Twisted Pair (90°C)

CASMO Part No.Core ConfigurationConductor Size (AWG)No. Of StrandsNom. Strand Dia. (mm)Nom. Ins. Thickness (mm)Nom. Jkt. Thickness (mm)Braid Coverage (%)Nom. O.D. (mm)Max. DCR @20°C (Ω/km)Nom. Cable Weight (kg/km)
1241151P26-TS2-XX1 × 22670.160.220.80854.415031
1241152P26-TS2-XX2 × 22670.160.220.80855.415043
1241153P26-TS2-XX3 × 22670.160.220.80855.815050
1241154P26-TS2-XX4 × 22670.160.220.80856.215057
1241156P26-TS2-XX6 × 22670.160.220.80857.015071
1241151P24-TS2-XX1 × 22470.2030.230.80854.794.235
1241152P24-TS2-XX2 × 22470.2030.230.80855.994.250
1241153P24-TS2-XX3 × 22470.2030.230.80856.394.260
1241154P24-TS2-XX4 × 22470.2030.230.80856.894.270
1241156P24-TS2-XX6 × 22470.2030.230.80857.794.289
1241151P22-TS2-XX1 × 22270.2540.230.80855.059.441
1241152P22-TS2-XX2 × 22270.2540.230.80856.459.460
1241153P22-TS2-XX3 × 22270.2540.230.80856.959.473
1241154P22-TS2-XX4 × 22270.2540.230.80857.459.485
1241156P22-TS2-XX6 × 22270.2540.230.80858.459.4111
1241151P20-TS2-XX1 × 220260.160.250.85855.636.749
1241152P20-TS2-XX2 × 220260.160.250.85857.136.774
1241153P20-TS2-XX3 × 220260.160.250.85857.736.791
1241154P20-TS2-XX4 × 220260.160.250.85858.336.7108

* "-TS2-" = tinned copper conductor with FT2 flame rating (standard). "-TS1-" = tinned copper conductor with VW-1 / FT1 flame rating (optional). § Part No. pair code: "NP" = N twisted pairs (2N total conductors, e.g. 6P = 6 twisted pairs / 12 cores). "-XX" = outer jacket color code: BK Black (standard), GY Grey, OR Orange, YW Yellow, BL Blue, RD Red. Custom jacket colors and core legends available on request.

  • "-TS2-" = tinned copper conductor with FT2 flame rating (standard). "-TS1-" = tinned copper conductor with VW-1 / FT1 flame rating (optional).
  • Part No. pair code: "NP" = N twisted pairs (2N total conductors, e.g. 6P = 6 twisted pairs / 12 cores). "-XX" = outer jacket color code: BK Black (standard), GY Grey, OR Orange, YW Yellow, BL Blue, RD Red. Custom jacket colors and core legends available on request.

Color Code Chart

  • Black / Red
  • Black / White
  • Black / Green
  • Black / Blue
  • Black / Brown
  • Black / Yellow

Related Categories