Control & Data Cables
Multi-conductor and twisted-pair cables for factory automation, instrumentation, machinery and rail transit — spanning DIN VDE 0812, UL AWM PUR and EN 50264 constructions in PVC, LSZH, PUR and cross-linked compounds.
Multi-conductor control, signal & specialised transit cables
Industrial control cabinets, sensor networks, CNC machinery and transit systems demand multi-conductor cables that preserve signal integrity under continuous flexing, electromagnetic interference and harsh chemical exposure. Rather than relying on one regional format, global OEMs select constructions across harmonised European designations (such as DIN VDE 0812 with DIN 47100 colour coding), North American UL AWM PUR-jacketed automation cables and specialised rolling-stock standards (EN 50264 / EN 45545-2).
Insulation and jacketing chemistry directly address the installation environment: flexible PVC with tinned-copper braid screening (such as LiYCY) handles general EMC cabinet and instrumentation links; polyethylene-insulated twisted pairs (such as Li2YCY-TP) lower mutual capacitance for RS-422 and RS-485 serial data; halogen-free LSZH builds (such as LiHCH) protect public buildings and enclosed spaces; oil- and abrasion-resistant PUR sheaths (such as LiY11Y and UL AWM PUR multicore cables) withstand cutting fluids and dynamic machinery duty; and electron-beam cross-linked halogen-free rolling-stock cables (such as 4GKW-AX Plus) meet demanding rail traction and fire-safety requirements.
CASMO engineers European and international control, data and transit cables to standard dimensional, EMC-screening and copper-weight profiles — offering automation builders a reliable, reference-only functional alternative comparable to widely specified series such as LAPP UNITRONIC®.
UNITRONIC® is a registered trademark of U.I. Lapp GmbH; CASMO CABLE LLC is an independent manufacturer not affiliated with or endorsed by LAPP. Always verify dimensional and test details against CASMO's specification sheet prior to substitution.
Control & Data Cable Products
- LIYCY — DIN VDE 0812 / DIN 47100 · PVC · -40°C to +80°C · 500V
- LIY11Y — DIN VDE 0812 / DIN 47100 · PVC · -40°C to +80°C · 500V
- LIHCH — DIN VDE 0812 / IEC 60754 · LSZH · -30°C to +80°C · 500V
- LI2YCY-TP — DIN VDE 0812 / DIN 47100 · PE · -40°C to +80°C · 250V
- 4GKW-AX PLUS FLEX — EN 50264-3-1 / EN 45545-2 · Halogen-Free XLPO · -40°C to +120°C · 1800/3000V
Related Standards, Materials & Applications
Frequently Asked Questions
- When should I choose a twisted-pair data cable like Li2YCY-TP over standard LiYCY?
- Choose polyethylene-insulated twisted-pair cables (such as Li2YCY-TP) for RS-422, RS-485 and high-speed differential data transmission where low mutual capacitance and crosstalk rejection are critical; use standard PVC LiYCY for general control and low-frequency signal wiring.
- When is a PUR jacket or LSZH compound preferred over standard PVC?
- Specify a polyurethane (PUR) outer sheath (such as LiY11Y or UL AWM PUR cables) wherever mineral oils, coolants, cutting fluids or severe mechanical abrasion degrade PVC. Specify halogen-free LSZH (such as LiHCH) in enclosed public buildings, tunnels or transit systems requiring low smoke and zero corrosive acid gases.
- Are CASMO DIN VDE 0812 control cables comparable to LAPP UNITRONIC® series?
- Yes — CASMO designs its DIN VDE 0812 and DIN 47100 control and data series to standard European outer diameters, shielding coverage and electrical characteristics for reference-only cross-selection. Always verify dimensional, electrical and approval details against CASMO's specification sheet prior to substitution.
- How do EN 50264 rolling-stock cables differ from standard factory control cables?
- Rolling-stock cables (such as 4GKW-AX Plus, 1.8/3 kV) use dual-layer electron-beam cross-linked, halogen-free insulation and sheathing qualified to EN 50264 and EN 45545-2 fire-safety classes for traction converters, bogies and passenger rail vehicles.