High-Temperature Ampacity & Derating Calculator

Calculate continuous wire ampacity and compound ambient temperature, harness/conduit bundling, and high-altitude derating across 80°C–550°C insulations (NEC Art. 310, Neher-McGrath, SAE AS50881, ISO 2533).

High-Temperature Ampacity & Derating Calculator Capabilities

Supported continuous insulation thermal classes: 80°C, 90°C, 105°C, 125°C, 150°C, 200°C, 250°C, 450°C, 550°C.

  • 9 thermal classes (80°C–550°C) via NEC 310.16–310.19 and Neher-McGrath
  • Compound ambient, NEC / SAE AS50881 bundle, and ISO 2533 altitude factors
  • Conduit, bundled air harness, and free-air modes (AWG, kcmil, mm²)
  • Automatic ASTM metallurgy pairing and CASMO series recommendations

Compound Thermal, Bundling, Metallurgy & Altitude Derating Model

Continuous allowable current is evaluated as I_derated = I_base × K_alloy × K_temp × K_bundle × K_alt across NEC Article 310, IEC 60287-1-1 / Neher–McGrath thermal scaling, SAE AS50881 fine-gauge harness ratings, and ISO 2533 / IEEE Std 738 high-altitude convective cooling. Sub-ambient correction follows NEC Tables 310.15(B)(1) and 310.15(B)(2) (capped at the 10°C floor and subject to NEC §310.14(A)(2) 3.0 m / 10 ft warm-zone limits).

NEC Tables 310.16–310.19 Base Ampacity Reference (90°C–250°C)

At 90°C (30°C ambient), 18 AWG through 750 kcmil follow NFPA 70 (NEC) Table 310.16 (≤3 current-carrying conductors in raceway/cable) and Table 310.17 (single insulated conductor in free air), with 28–20 AWG calibrated to SAE AS50881 Fig. 3. At 150°C, 200°C, and 250°C (40°C ambient), direct NEC Tables 310.18 and 310.19 cover strictly 14 AWG through 4/0 AWG — where 150°C and 200°C apply to copper conductors and the 250°C column is tabulated on an ASTM B355 Class 2 (2% Nickel-Plated Copper, -NS-) basis. Sizes outside 14 AWG–4/0 AWG and extreme 450°C–550°C MGT classes scale continuously via NEC §310.15(C) / Neher–McGrath.

Wire SizeArea (mm²)90°C Raceway (A)90°C Free Air (A)150°C Raceway Cu (A)150°C Free Air Cu (A)200°C Raceway Cu (A)200°C Free Air Cu (A)250°C Raceway 2% NPC (A)250°C Free Air 2% NPC (A)Standard Scope
28 AWG0.08103.24.8——————SAE AS50881 Fig. 3 / IEC 60287 Harness Basis
26 AWG0.12884.56.5——————SAE AS50881 Fig. 3 / IEC 60287 Harness Basis
24 AWG0.204769——————SAE AS50881 Fig. 3 / IEC 60287 Harness Basis
22 AWG0.32558.512.5——————SAE AS50881 Fig. 3 / IEC 60287 Harness Basis
20 AWG0.517611.517——————SAE AS50881 Fig. 3 / IEC 60287 Harness Basis
18 AWG0.82301418——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
16 AWG1.3091824——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
14 AWG2.0812535344636543959NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
12 AWG3.3093040436045685478NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
10 AWG5.26140555580609073107NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
8 AWG8.3665580761068312493142NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
6 AWG13.307510596155110165117205NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
4 AWG21.1595140120190125220148278NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
3 AWG26.67110165143214152252166327NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
2 AWG33.63130190160255171293191381NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
1 AWG42.41145220186293197344215440NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
1/0 AWG53.48170260215339229399244532NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
2/0 AWG67.43195300251390260467273591NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
3/0 AWG85.03225350288451297546308708NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
4/0 AWG107.22260405332529346629361830NEC Tables 310.16–310.19 Direct (14 AWG–4/0 AWG)
250 kcmil126.68290455——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
300 kcmil152.01320505——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
350 kcmil177.35350570——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
400 kcmil202.68380615——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
500 kcmil253.35430700——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
600 kcmil304.02475780——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
700 kcmil354.70520855——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath
750 kcmil380.03535885——————NEC 310.16/310.17 Direct (90°C); >90°C via NEC 310.15(C) Neher–McGrath

NEC Table 310.15(C)(1) Multi-Conductor & Harness Bundling Factors

Number of Current-Carrying ConductorsAdjustment Multiplier (K_bundle)Application Scope
1–3 conductors1.00× (100%)Baseline for ≤3 current-carrying conductors in raceway/cable or unbundled single wire in free air
4–6 conductors0.80× (80%)Applies to raceways, multi-core cables, and open-air harnesses bundled longer than 600 mm (24 in.)
7–9 conductors0.70× (70%)Applies to raceways, multi-core cables, and open-air harnesses bundled longer than 600 mm (24 in.)
10–20 conductors0.50× (50%)Applies to raceways, multi-core cables, and open-air harnesses bundled longer than 600 mm (24 in.)
21–30 conductors0.45× (45%)Applies to raceways, multi-core cables, and open-air harnesses bundled longer than 600 mm (24 in.)
31–40 conductors0.40× (40%)Applies to raceways, multi-core cables, and open-air harnesses bundled longer than 600 mm (24 in.)
41+ conductors0.35× (35%)Applies to raceways, multi-core cables, and open-air harnesses bundled longer than 600 mm (24 in.)

CASMO High-Temperature Cable Families & Conductor Metallurgy Pairing (80°C–550°C+)

Thermal ClassCASMO Insulation & Product SeriesStandard Conductor & SuffixEngineering & Manufacturing Notes
80°C–105°CPVC / SR-PVC Hook-Up, XLPE / LSZH & High-Flex PUR / TPEBare Copper (-AS-) or Tinned Copper (-TS- / -TS2- / -TS1-)UL 1007 / 1015 / 1061 & JASO AVSS PVC (-TS-), UL 3173 / 3385 & XHHW-2 XLPE/LSZH (-TS2- FT2 / -TS1- VW-1), and UL 20233 / 20549 drag-chain PUR/TPE (100% PFAS-Free).
125°C–150°CXLPE / Halogen-Free XLPO, 150°C Silicone & CASRAD™ XP 150 / XE 150Tinned Copper (-TS- / -TS2-) or Silver-Plated Copper (-SS-)PFAS-free UL 3173 / 3266 / 3321, EN 50618 solar, ISO 19642 automotive, and UL 3212 silicone (-TS2-), plus aerospace CASRAD™ XP 150 (SAE AS 81044 dual-wall polyalkene/PVDF) and CASRAD™ XE 150 (SAE AS 22759 XL-ETFE).
200°CUltra-Flex Silicone Rubber (SiR), CASRAD™ XE 200 & PTFE / FEPSilver-Plated Copper (-SS-) or 2% Nickel-Plated Copper (-NS-)PFAS-free UL 3122 / 3135 / 3239 / 3512 EV & motor silicone, radiation/fluid-resistant CASRAD™ XE 200 (SAE AS 22759 XL-ETFE), and UL 1180 / 1199 PTFE & UL 1330 / 1332 FEP (NEMA HP3 / HP4).
250°C–260°CCASPEEK™ 260 (PEEK), Extruded PTFE & Melt-Extruded PFA / Wrapped TGGT2% Nickel-Plated Copper (-NS-, ASTM B355 Class 2 standard)100% PFAS-free, radiation-tolerant CASPEEK™ 260 (−65°C to +260°C, UL 94 V-0); UL 1570 / 1659 / 1815 / 10362 & NEMA HP3 extruded PTFE within CASMO's ≤ 6.5 mm extruded PTFE O.D. envelope; and melt-extruded UL 1726 / 1727 / 10393 PFA or wrapped UL 5196 / 5256 TGGT above 6.5 mm O.D.
450°C–550°C+MGT Mica + Fiberglass & High-Silica / Quartz Extreme-Heat Braid27% Nickel-Coated Copper (-NC27-) or Pure Nickel 200 (-N-)UL 5107 / 5128 / 5359 / 5360 / 5561 MGT furnace & heater leads (-NC27- standard for 450°C–550°C; specify silicone/uncoated non-PTFE braid finish when PFAS-free compliance is required) and 700°C–1000°C+ High-Silica / Quartz leads with ASTM B160 Pure Nickel 200 (-N-).

Engineering Notice & Disclaimer

All online wire size converters, conductor resistance (DCR), AC/DC voltage-drop, high-temperature ampacity and derating, and related technical calculators hosted on casmocable.com are provided by CASMO CABLE LLC strictly for preliminary engineering estimation and general informational reference on an "as-is" and "as-available" basis without warranty of accuracy, completeness, or fitness for any particular purpose. Calculated values are derived from nominal geometric cross-sections, reference material and raceway impedance models, and generalized thermal, bundling, and altitude derating curves (ASTM B258, IEC 60228, ASTM B3–B355, UNS N02200, NEC Ch. 9 and Art. 310, IEC 60287 and 60364-5-52, SAE AS50881, and ISO 2533 / IEEE 738) and do not account for lot-specific manufacturing tolerances, harmonic heating, exact enclosure or multi-cable finite-element heat dissipation, connector or crimp termination contact resistance and terminal temperature limits, or local electrical code and Authority Having Jurisdiction (AHJ) installation requirements. Online calculator outputs do not constitute binding product specifications, safety certifications, or professional engineering sign-off. Before finalizing any specification, safety-critical or regulated end-use qualification, or production order, users are solely responsible for verifying guaranteed electrical, thermal, and dimensional limits against CASMO's published A4 specification sheets, approved engineering drawings, and physical sample testing. CASMO CABLE LLC assumes no liability for design decisions, losses, or indirect or consequential damages arising from use of or reliance upon these online tools. See Terms and Conditions of Sale (Section 10) for full legal terms.

Frequently Asked Questions

Which wire sizes use direct NEC Article 310 tables versus NEC 310.15(C) Neher–McGrath thermal scaling?
At 90°C (30°C ambient), 18 AWG through 750 kcmil map directly to NFPA 70 (NEC) Tables 310.16 (raceway/cable) and 310.17 (free air). At 150°C, 200°C, and 250°C (40°C ambient), NEC Tables 310.18 and 310.19 cover 14 AWG through 4/0 AWG only (with the 250°C column tabulated for ASTM B355 Class 2 nickel-coated copper). Intermediate classes (80°C, 105°C, 125°C), fine harness gauges (28–20 AWG, calibrated to SAE AS50881 Fig. 3), heavy kcmil sizes above 4/0 AWG, and 450°C–550°C MGT furnace leads scale via the NEC 310.15(C) / IEC 60287-1-1 Neher–McGrath equation.
Why must conductor metallurgy step up from tinned copper to silver-plated, 2% NPC, 27% NCC, or Pure Nickel 200 at high temperatures?
Tin melts at 231.9°C and forms brittle Cu–Sn intermetallics above 150°C–180°C continuous service, while bare copper oxidizes rapidly in hot air. Silver-Plated Copper (-SS-, 100% IACS) serves up to 200°C; 2% Nickel-Plated Copper (-NS-, ASTM B355 Class 2, 96% IACS) handles 250°C–260°C fluoropolymer and PEEK cables; 27% Nickel-Coated Copper (-NC27-, ASTM B355 Class 27, 71% IACS min, ~0.84× ampacity factor) blocks oxygen diffusion at 450°C–550°C; and Pure Nickel 200 (-N-, ASTM B160, Curie curve, ~0.37× ampacity factor) serves above 550°C.
How do ambient temperature, harness bundling, and high-altitude elevation derating combine?
Derated ampacity equals I_base × K_alloy × K_temp × K_bundle × K_alt. Ambient correction follows NEC Tables 310.15(B)(1) and 310.15(B)(2) (capped at the 10°C sub-ambient row, subject to NEC 310.14(A)(2) 3.0 m / 10 ft warm-zone limits). NEC Table 310.15(C)(1) bundling multipliers apply both in raceways/cables and to open-air wire harnesses bundled longer than 600 mm (24 in.), whereas a single isolated wire in free air keeps K_bundle = 1.00. Above 1,000 m (or sea level in aerospace mode), ISO 2533 air-density reduction lowers IEEE Std 738 convective cooling (~P^0.5) while thermal radiation remains altitude-invariant.
Why do 250°C recommendations switch away from extruded PTFE when finished outer diameter exceeds 6.5 mm?
Unlike melt-extruded PFA, FEP, or PEEK, PTFE does not melt-flow above 327°C and must be ram-paste extruded from finite preform billets and sintered. Above CASMO's 6.5 mm extruded PTFE outer-diameter process boundary (typically crossed at 6 AWG heavy-wall UL 1199 ~6.86 mm and 16 mm² rope-lay power builds), recommendations automatically transition to melt-extruded PFA, PFAS-free CASPEEK™ 260 (PEEK), or helically wrapped PTFE/fiberglass (TGGT UL 5196 / 5256).