Voltage Drop Calculator (AC & DC)

Size minimum safe conductors or verify voltage drop across DC, single-phase AC, and three-phase AC circuits (AWG, kcmil, and metric mm²) with NEC Ch. 9 Table 9 reactance, IEC 60287 AC impedance, and parallel runs.

AC & DC Voltage Drop Calculator Capabilities

  • Safe wire sizing and fixed-gauge check across AWG, kcmil, and mm²
  • DC (2-wire / 1-wire), 1Φ AC, and 3Φ AC drop with IEEE 141 phasor
  • IEC 60287 impedance in PVC, Al, and steel raceways + parallel solver
  • 6 ASTM copper/nickel alloys (−65°C to +1000°C) with Worksheet handoff

AC & DC Circuit Voltage Drop Equations (NEC Ch. 9 Table 9, IEC 60364-5-52 & IEEE Std 141)

  • DC Loop & Single-Wire Chassis Return: ΔV_DC = k × I × (L / 1000) × R_dc(T), where k = 2 for standard two-wire supply-and-return loops (2 × L) and k = 1 for single-wire chassis/busbar return circuits (1 × L).
  • Single-Phase & Three-Phase AC Effective Impedance (NEC Chapter 9 Table 9 Note 2 & IEC 60364-5-52 Annex G): ΔV_approx = k × I × (L / 1000) × (R_ac × cos φ + X_L × sin φ), where k = 2 for 1-phase AC and k = √3 (≈ 1.732) for balanced 3-phase line-to-line circuits, incorporating IEC 60287-1-1:2023 §2.1.2–2.1.5 skin effect (y_s), proximity effect (y_p), and raceway geometries (Non-Magnetic PVC / RNC Conduit (NEC Table 9); Magnetic Steel Conduit (+25% X_L & Pipe Loss · NEC Table 9); Aluminum Conduit (Eddy Loss · NEC Table 9); Multi-Core Cable / Touching Trefoil (Compact X_L); Spaced Single Conductors in Open Tray (Higher X_L)).
  • Exact Receiving-End Phasor Drop (IEEE Std 141 Eq. 3-6): V_load = √(V_source² − [k × I × (L / 1000) × (X_L × cos φ − R_ac × sin φ)]²) − k × I × (L / 1000) × (R_ac × cos φ + X_L × sin φ), with N-set parallel feeder division (I_set = I_total / N, 1× to 8× sets per phase) and total circuit I²R_ac power dissipation.

NEC Chapter 9, Table 9 — 60 Hz AC Resistance & Conduit Reactance Reference (28 AWG to 750 kcmil)

Reference 60 Hz three-phase copper conductor resistance at 75°C and line-to-neutral inductive reactance X_L (Ω/km) in non-magnetic PVC/RNC conduit versus magnetic steel conduit. For 50 Hz systems, inductive reactance scales by 50 / 60.

Wire SizeArea (mm²)R_dc @75°C Cu (Ω/km)60 Hz R_ac PVC Conduit (Ω/km)60 Hz R_ac Steel Conduit (Ω/km)60 Hz X_L Non-Magnetic PVC/Al (Ω/km)60 Hz X_L Magnetic Steel (Ω/km)Standard Basis
28 AWG0.0810264.1167264.1167264.11670.2500.313GMD Inductance Continuation (60 Hz)
26 AWG0.1288166.1046166.1046166.10460.2400.300GMD Inductance Continuation (60 Hz)
24 AWG0.2047104.4642104.4642104.46420.2300.288GMD Inductance Continuation (60 Hz)
22 AWG0.325565.698265.698265.69820.2200.275GMD Inductance Continuation (60 Hz)
20 AWG0.517641.318041.318041.31800.2100.263GMD Inductance Continuation (60 Hz)
18 AWG0.823025.985125.985225.98520.2030.254GMD Inductance Continuation (60 Hz)
16 AWG1.30916.342216.342216.34230.1970.246GMD Inductance Continuation (60 Hz)
14 AWG2.08110.277710.277810.27780.1900.240NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
12 AWG3.3096.46376.46386.46380.1770.223NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
10 AWG5.2614.06514.06524.06530.1640.207NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
8 AWG8.3662.55662.55672.55680.1710.213NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
6 AWG13.301.60781.60811.60830.1670.210NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
4 AWG21.151.01121.01161.01190.1570.197NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
3 AWG26.670.80190.80240.80280.1540.194NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
2 AWG33.630.63590.63660.63710.1480.187NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
1 AWG42.410.50430.50510.50570.1510.187NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
1/0 AWG53.480.39990.40090.40170.1440.180NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
2/0 AWG67.430.31720.31840.31940.1410.177NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
3/0 AWG85.030.25150.25310.25440.1380.171NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
4/0 AWG107.220.19950.20140.20300.1350.167NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
250 kcmil126.680.16880.17120.17300.1350.171NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
300 kcmil152.010.14070.14350.14570.1350.167NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
350 kcmil177.350.12060.12380.12640.1310.164NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
400 kcmil202.680.10550.10920.11210.1310.161NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
500 kcmil253.350.08440.08890.09250.1280.157NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
600 kcmil304.020.07030.07560.07980.1280.157NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
700 kcmil354.700.06030.06630.07100.1260.157NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)
750 kcmil380.030.05630.06260.06760.1250.157NFPA 70 (NEC) Ch. 9 Table 9 (60 Hz)

Engineering Notice & Disclaimer

All online wire size converters, conductor resistance (DCR), AC/DC voltage-drop, high-temperature ampacity and derating, and related technical calculators hosted on casmocable.com are provided by CASMO CABLE LLC strictly for preliminary engineering estimation and general informational reference on an "as-is" and "as-available" basis without warranty of accuracy, completeness, or fitness for any particular purpose. Calculated values are derived from nominal geometric cross-sections, reference material and raceway impedance models, and generalized thermal, bundling, and altitude derating curves (ASTM B258, IEC 60228, ASTM B3–B355, UNS N02200, NEC Ch. 9 and Art. 310, IEC 60287 and 60364-5-52, SAE AS50881, and ISO 2533 / IEEE 738) and do not account for lot-specific manufacturing tolerances, harmonic heating, exact enclosure or multi-cable finite-element heat dissipation, connector or crimp termination contact resistance and terminal temperature limits, or local electrical code and Authority Having Jurisdiction (AHJ) installation requirements. Online calculator outputs do not constitute binding product specifications, safety certifications, or professional engineering sign-off. Before finalizing any specification, safety-critical or regulated end-use qualification, or production order, users are solely responsible for verifying guaranteed electrical, thermal, and dimensional limits against CASMO's published A4 specification sheets, approved engineering drawings, and physical sample testing. CASMO CABLE LLC assumes no liability for design decisions, losses, or indirect or consequential damages arising from use of or reliance upon these online tools. See Terms and Conditions of Sale (Section 10) for full legal terms.

Frequently Asked Questions

What is the difference between the NEC Chapter 9 Table 9 effective impedance formula and the IEEE Std 141 exact phasor drop?
NEC Chapter 9 Table 9 Note 2 and IEC 60364-5-52 Annex G approximate voltage drop using the in-phase projection ΔV ≈ k · I · L · (R_ac·cos φ + X_L·sin φ), where k = 2 for single-phase or 2-wire DC and √3 for balanced three-phase line-to-line circuits. IEEE Std 141 (Red Book) Eq. 3-6 additionally accounts for the quadrature voltage shift I · L · (X_L·cos φ − R_ac·sin φ) between source and load phasors; below 5% voltage drop the two methods agree within ~0.15%, while Exact Phasor mode captures angular sag on heavy low-power-factor motor-starting or long feeder runs.
Why can a large three-phase AC feeder fail a voltage-drop target even at 750 kcmil, requiring parallel conductors?
While DC and AC resistance decrease inversely with conductor cross-section, inductive reactance X_L depends logarithmically on conductor spacing over geometric mean radius (remaining ~0.125 Ω/km in non-magnetic conduit and ~0.157 Ω/km in magnetic steel conduit even at 750 kcmil). At lagging power factors such as 0.85 (sin φ ≈ 0.527), reactive drop X_L·sin φ creates an irreducible single-cable drop floor; splitting the load across N parallel sets per phase divides both R_ac and X_L by N, and switching from steel to non-magnetic PVC conduit lowers X_L by ~20%.
When should DC circuits use 2-Way Loop (2 × L) versus 1-Way Single-Wire (1 × L) mode?
Standard two-wire DC power feeds (such as 1500V solar strings, 800V EV battery interconnects, and industrial 24V/48V control loops) carry current out and back through paired conductors over one-way distance L, so total conductor path length is 2 × L. Use 1-Way mode only when sizing a single insulated feed leg whose return path is an independently engineered low-impedance vehicle chassis, airframe structure, or heavy copper busbar.
How does this calculator differ from the Conductor Resistance (DCR) & Voltage Drop Calculator?
The DCR & Metallurgy tool evaluates temperature-adjusted DC resistance (Ω/km, Ω/kft) from −190°C to +1200°C for a known wire size. This AC/DC Voltage Drop Calculator solves the inverse circuit-sizing problem — finding the minimum compliant AWG/kcmil or IEC/ISO metric cross-section (and 2×–8× parallel sets) for DC, 1-phase AC, and 3-phase AC loads with IEC 60287-1-1 skin/proximity effects, NEC Chapter 9 Table 9 conduit reactance, and kW/kVA load conversion.