BUS CAN FD

BUS CAN FD is a CASMO industrial fieldbus cable for Industrial Fieldbus. Foam PE insulated, -40°C to +80°C, 250V. 120 Ω continuous-flex drag-chain (FD) industrial CAN, CANopen and CAN FD bus cable with 19-strand bare copper conductors, cellular PE insulation, tinned-copper braid shield and oil-re…

120 Ω continuous-flex drag-chain (FD) industrial CAN, CANopen and CAN FD bus cable with 19-strand bare copper conductors, cellular PE insulation, tinned-copper braid shield and oil-resistant halogen-free violet PUR sheath.

Key Ratings

  • BUS CAN FD: · Temperature -40°C to +80°C · Rated Voltage 250V · Test Voltage 1500V

Construction

Conductor
Bare Copper · Flexible Stranded
Core Insulation
Foamed · Foam PE
Cabling
Twisted
Core Identification
1×2: White / Brown; 2×2: White / Brown, Green / Yellow (DIN 47100)
Shield
Braid · Tinned copper braid
Jacket
Extruded · PUR/TPU

Characteristics

  • Continuous Flexing Temperature: -30°C to +70°C
  • Characteristic Impedance: 120 Ω ± 12 Ω (at 1 MHz)
  • Mutual Capacitance: Approx. 40 nF/km (at 800 Hz)
  • Velocity of Propagation: Approx. 76%
  • Continuous-Flex Durability: Designed to withstand repeated bending cycles in cable carriers and continuously moving machinery.
  • Oil Resistance: Resistant to oil exposure, helping maintain the integrity of the cable covering in oily environments.
  • Abrasion Resistance: Resistant to abrasion, helping protect the cable surface against wear caused by rubbing and handling.
  • EMC Interference Shielding: Metallic shielding helps suppress electromagnetic interference and maintain signal integrity in electrically noisy environments.

Applications

  • Cable Carriers and Moving Machinery: For dynamic signal and control routing in drag chains, gantries, linear axes and automated handling equipment.
  • Fieldbus and Serial Data Networks: For differential serial and fieldbus communication links between programmable controllers, distributed I/O modules, drives and field devices.

Standards & Compliance

  • Standard: ISO 11898-2
  • Fire Performance: FT2
  • RoHS: Compliant
  • REACH: Compliant

Specification Data

CASMO Part No.Conductor Size (mm²)No. Of StrandsNom. Strand Dia. (mm)Nom. Ins. Thickness (mm)Nom. Core O.D. (mm)Min. Braid Coverage (%)Nom. Jkt. Thickness (mm)Nom. O.D. (mm)Max. DCR @20°C (Ω/km)
1230020.25/19-1P-AS-VT1×2×0.25190.130.551.75800.956.479.8
1230020.25/19-2P-AS-VT2×2×0.25190.130.551.75801.107.879.8
1230020.34/19-1P-AS-VT1×2×0.34190.150.622.00801.006.961.0
1230020.34/19-2P-AS-VT2×2×0.34190.150.622.00801.158.661.0
1230020.5/19-1P-AS-VT1×2×0.5190.180.752.40801.108.040.5
1230020.5/19-2P-AS-VT2×2×0.5190.180.752.40801.2510.040.5

* "-AS-" = 19-strand flexible bare copper conductor for continuous-flex drag-chain (FD) service; "-1P" / "-2P" = number of twisted pairs; "-VT" = violet (RAL 4001) PUR outer sheath (standard). † Max. DCR @20°C is specified per single conductor; maximum DC loop resistance equals 2 × single-conductor DCR (159.6 / 122.0 / 81.0 Ω/km for 0.25 / 0.34 / 0.5 mm²). Compatible with Classical CAN, CANopen, and CAN FD physical layers (ISO 11898-2). ‡ Standard halogen-free PUR jacket meets FT2 flame rating; low-halogen VW-1 / FT1 jacket available upon request.

  • "-AS-" = 19-strand flexible bare copper conductor for continuous-flex drag-chain (FD) service; "-1P" / "-2P" = number of twisted pairs; "-VT" = violet (RAL 4001) PUR outer sheath (standard).
  • Max. DCR @20°C is specified per single conductor; maximum DC loop resistance equals 2 × single-conductor DCR (159.6 / 122.0 / 81.0 Ω/km for 0.25 / 0.34 / 0.5 mm²). Compatible with Classical CAN, CANopen, and CAN FD physical layers (ISO 11898-2).
  • Standard halogen-free PUR jacket meets FT2 flame rating; low-halogen VW-1 / FT1 jacket available upon request.