TIA/EIA-485 — Electrical Characteristics of Balanced Digital Multipoint Systems
Balanced differential multipoint serial interface standard underpinning industrial RS-485, Modbus RTU, BACnet MS/TP, and DMX512 low-capacitance 120 Ω data cables.
Standard · Telecommunications Industry Association / Electronic Industries Alliance
What is TIA/EIA-485?
Commonly known across industry as RS-485, this specification defines balanced differential voltage signaling capable of linking up to 32 unit loads—or 128 to 256 fractional-load transceivers—across noisy industrial trunks up to 1200 m. While the standard defines transceiver thresholds rather than a single mandatory jacket polymer, reliable multi-drop communication over hundreds of meters requires a dedicated 120 Ω low-capacitance twisted-pair cable rather than high-capacitance general-purpose audio or control wire.
Industrial RS-485 cables pair 24 AWG or 22 AWG stranded tinned-copper conductors with low-permittivity foam polyethylene insulation, achieving ~38–45 pF/m mutual capacitance, paired with 100% aluminum/polyester foil, a tinned-copper drain wire, and ≥85% tinned-copper braid shielding to protect differential A/B lines and common reference conductors from motor and switchgear transients.
Key Technical Requirements
| Parameter | Requirement | Notes |
|---|---|---|
| Characteristic impedance | 120 Ω nominal (±10%–12%) | Matched to 120 Ω end-of-line termination resistors |
| Mutual capacitance | ≤ 42–50 pF/m typical (foam polyolefin dielectric) | Preserves slew rate across 1200 m trunks |
| Circuit topologies | 1 Pair + Ground (2-wire half-duplex) · 2 Pair + Ground (4-wire full-duplex) | Dedicated signal-common reference prevents ground-potential lockup |
| Dual EMI shield | 100% Al/PET foil + drain wire + ≥85% tinned-copper braid | Broadband RF foil + low-frequency braid coverage |
| Industrial protocols | Modbus RTU · BACnet MS/TP · PROFIBUS RS-485 · Encoder feedback | Available in PVC, UV-stabilized PE, LSZH, and PUR |
TIA/EIA-485 Products
- BUS RS-485 — TIA/EIA-485-A · Foam PE / PVC · -30°C to +80°C · 300V
- BUS RS-485 FD — TIA/EIA-485-A · Foam PE / PUR/TPU · -40°C to +80°C · 300V
- BUS RS-485 OUTDOOR — TIA/EIA-485-A · Foam PE / PE · -40°C to +80°C · 300V
Insulation Materials in This Standard
Frequently Asked Questions
- Why does a 2-wire RS-485 / Modbus RTU network often need a 3-conductor (1P + 1C) cable?
- Differential RS-485 transceivers tolerate only −7 V to +12 V common-mode ground offset. Including a dedicated third insulated signal-reference conductor ties transceiver grounds together without routing fault currents through the EMI shield.
- Why do Cat5e Ethernet cables or PVC hook-up wires cause RS-485 communication dropouts?
- Cat5e has 100 Ω impedance and solid 24 AWG cores prone to vibration fatigue in industrial machinery, while PVC control cables exceed 100–150 pF/m capacitance and ~70 Ω impedance, distorting waveforms on long multi-drop runs.
- When should I specify a 2-pair RS-485 cable?
- Choose a 2-pair 120 Ω cable for full-duplex 4-wire RS-485/RS-422 links, or for 2-wire half-duplex networks where the second twisted pair supplies isolated 24 V DC power alongside data.